Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM03996
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/06/2018 | DAVID RIVERA | ZONING | REVIEW | Passed | |
| 06/14/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/18/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 06/21/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Single and Three line diagrams. The secondary feeders to the new 1600 amp SES are shown as 1 set of 3-500 kcmil conductors. Per NEC 310.15b(16) 500 kcmil Cu is rated at 380 amps per the 75deg. Column. Justify that this adequate to cover the load for the service. #2. Provide for GFI protection for the main service switch rated at 1600 amps Per NEC 230.95. Ref: 2012 IBC sec 107.2.1, 2011 NEC |