Permit Number: T18CM03996
Parcel: 14016006A

Address:
5102 S CHERRY AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM03996
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2018 MARTIN BROWN FIRE REVIEW Approved
06/06/2018 DAVID RIVERA ZONING REVIEW Passed
06/14/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/18/2018 JOHN VAN WINKLE ENGINEERING REVIEW Passed
06/21/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Single and Three line diagrams. The secondary feeders to the new 1600 amp SES are shown as 1 set of 3-500 kcmil conductors. Per NEC 310.15b(16) 500 kcmil Cu is rated at 380 amps per the 75deg. Column. Justify that this adequate to cover the load for the service.
#2. Provide for GFI protection for the main service switch rated at 1600 amps Per NEC 230.95.
Ref: 2012 IBC sec 107.2.1, 2011 NEC