Permit Number: T18CM03878
Parcel: 119180820

Address:
802 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM03878
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/12/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response. 2nd Review.
#1. There was no response found in the 2nd submittal as requested per the 1st review.
#2. There is no evidence in this 2nd submittal that the proposed exterior lighting meets the requirement of the 2012 Tucson/Pima County Outdoor Lighting Code. See comments for the 1st review. The Tucson/Pima County Outdoor Lighting Code is not to be confused with the 2012 IECC requirements.
#3. Be advised that the luminaire cut sheets shows the luminaires selected have a color temperature output rating of 4000K. This is in violation section 402.1 Not to exceed 3500K.
#4. Provide the expiration date for the registrant seal.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, 2012 Tucson/Pima County Outdoor Lighting Code.