Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM03878
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/29/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/12/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 2nd Review. #1. There was no response found in the 2nd submittal as requested per the 1st review. #2. There is no evidence in this 2nd submittal that the proposed exterior lighting meets the requirement of the 2012 Tucson/Pima County Outdoor Lighting Code. See comments for the 1st review. The Tucson/Pima County Outdoor Lighting Code is not to be confused with the 2012 IECC requirements. #3. Be advised that the luminaire cut sheets shows the luminaires selected have a color temperature output rating of 4000K. This is in violation section 402.1 Not to exceed 3500K. #4. Provide the expiration date for the registrant seal. Ref; 2012 IBC sec 107.2.1, 2011 NEC, 2012 Tucson/Pima County Outdoor Lighting Code. |