Permit Number: T18CM03878
Parcel: 119180820

Address:
802 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM03878
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2018 MARTIN BROWN FIRE REVIEW Approved
06/04/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet E01; Pole Mounted Base Detail: A note on this detail indicates an attached structural Sheet S-1. Please attach that sheet to the drawing set.
2. Sheet S-1; Design Criteria: Please revise the building code to the 2012 IBC and verify all references to that code.
3. General: Please provide written responses to all review comments.
06/08/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide full compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. See section 104.2 for plan submittal requirements. Include a complete luminaire schedule, parcel size, lighting area and option used, lumen calcs including existing fixtures, shielding information, curfew lighting controls if applicable, evidence on the plans that the proposed new and retro - fitted lighting complies with this code.
#2. Provide the expiration date for the registrant seal.
#3. Designate a branch circuit and panel (NEC 408.4) for the luminaires requiring new wiring. Also show the panel location and provide a complete panel schedule including load calcs.
Ref 2012 IBC 107.2.1, Tucson/Pima County Outdoor Lighting Code, 2011 NEC