Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM03878
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/21/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/04/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet E01; Pole Mounted Base Detail: A note on this detail indicates an attached structural Sheet S-1. Please attach that sheet to the drawing set. 2. Sheet S-1; Design Criteria: Please revise the building code to the 2012 IBC and verify all references to that code. 3. General: Please provide written responses to all review comments. |
06/08/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide full compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. See section 104.2 for plan submittal requirements. Include a complete luminaire schedule, parcel size, lighting area and option used, lumen calcs including existing fixtures, shielding information, curfew lighting controls if applicable, evidence on the plans that the proposed new and retro - fitted lighting complies with this code. #2. Provide the expiration date for the registrant seal. #3. Designate a branch circuit and panel (NEC 408.4) for the luminaires requiring new wiring. Also show the panel location and provide a complete panel schedule including load calcs. Ref 2012 IBC 107.2.1, Tucson/Pima County Outdoor Lighting Code, 2011 NEC Dan.santacruz@tucsonaz.gov |