Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheets E1.1, E2.5, E2.6.
(a) The exterior lighting lumen calcs do not add up correctly. Please revise.
(b) The color temperature for the 'HH' led lighting is not indicated.
(c) A special inspection is required per sec 106.2.1. Also specify this on the plan as required per sec 104.2.2.
Ref; 2012 Tucson/Pima County Outdoor Lighting Code.