Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T18CM03866
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan Sheets E1.1, E2.5, E2.6. (a) The exterior lighting lumen calcs do not add up correctly. Please revise. (b) The color temperature for the 'HH' led lighting is not indicated. (c) A special inspection is required per sec 106.2.1. Also specify this on the plan as required per sec 104.2.2. Ref; 2012 Tucson/Pima County Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/03/2018 | SVALENZ1 | OUT TO CUSTOMER | Completed |