Permit Number: T18CM03851
Parcel: 10308001Q

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T18CM03851
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2019 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Approved
06/25/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed
06/25/2019 ELISA HAMBLIN ZONING REVIEW Passed
06/25/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The electrical plans call out 100 amp 480 volt OCPD for the 25KVA transformer. Please verify this is not oversized for this application.
2. The Line Diagram shows panel 'A' with a 60 amp MCB. The panel schedule shows an 80 amp MCB. Please clarify.
3. Indicate all feeder conduits, conductor sizes and types including the electrical equipment on the plans.
4. Provide a complete grounding detail for the electrical service and the 25KVA transformer.
5. Show the location of the 400 amp electrical service.
6. Please provide full compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting.
7. Provide compliance for the 2018 IECC for the lighting.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
06/25/2019 MARTIN BROWN FIRE REVIEW Approved
07/02/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/08/2019 AVAUGHN1 OUT TO CUSTOMER Completed