Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T18CM03851
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/25/2019 | RMCCOY1 | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/25/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
06/25/2019 | ELISA HAMBLIN | ZONING | REVIEW | Passed | |
06/25/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The electrical plans call out 100 amp 480 volt OCPD for the 25KVA transformer. Please verify this is not oversized for this application. 2. The Line Diagram shows panel 'A' with a 60 amp MCB. The panel schedule shows an 80 amp MCB. Please clarify. 3. Indicate all feeder conduits, conductor sizes and types including the electrical equipment on the plans. 4. Provide a complete grounding detail for the electrical service and the 25KVA transformer. 5. Show the location of the 400 amp electrical service. 6. Please provide full compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting. 7. Provide compliance for the 2018 IECC for the lighting. Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
06/25/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/02/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/08/2019 | AVAUGHN1 | OUT TO CUSTOMER | Completed |