Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM03851
Parcel: 10308001Q

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM03851
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change The following previous comments were not addressed as required.
1. Sheet 0; Open Bay Office: The licensed structural engineer of record signed the original submittal of these documents on 9-22-12 with an expiration of his seal noted as 06/30/15. This information must be updated and the drawings must be restamped, signed, and dated.
2. Sheet 0; Open Bay Office (Applicable Codes): This list references the 2009 IBC, the 2009 IMC, the 2009 IECC, and the 2008 NEC. Please update these to the 2012 IBC, IMC, and IECC, and the 2011 NEC. Verify this submittal meets all of the requirements of the updated codes.
3. Sheet 6; Installation Instructions: Note 1 indicates anchors to be installed per structural calculations. Please provide structural calculations for the structure and indicate anchor locations on a plan.
4. General: Please provide a site plan indicating the location of this structure. Provide separation distances from this structure to property lines, other buildings, etc. If this information is indicated on another sheet in this submittal, please reference this structure to that sheet.
5. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
10/31/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. No written response to the electrical plan review comments as requested per the last 2 plan reviews.
#2. As well as no compliance to the previous electrical plan review comments, the main circuit breaker for panel "W11" is undersized. Please clarify.
Ref; 2012 IBC sec 107.2.1, 2011 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/12/2018 AVAUGHN1 APPROVAL SHELF Completed
12/12/2018 AVAUGHN1 OUT TO CUSTOMER Completed
12/12/2018 AVAUGHN1 REJECT SHELF Completed