Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM03851
Parcel: 10308001Q

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM03851
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2018 MARTIN BROWN FIRE REVIEW Approved
06/06/2018 DAVID RIVERA ZONING REVIEW Approved
06/14/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 0; Open Bay Office: The licensed structural engineer of record signed the original submittal of these documents on 9-22-12 with an expiration of his seal noted as 06/30/15. This information must be updated and the drawings must be restamped, signed, and dated.
2. Sheet 0; Open Bay Office (Applicable Codes): This list references the 2009 IBC, the 2009 IMC, the 2009 IECC, and the 2008 NEC. Please update these to the 2012 IBC, IMC, and IECC, and the 2011 NEC. Verify this submittal meets all of the requirements of the updated codes.
3. Sheet 6; Installation Instructions: Note 1 indicates anchors to be installed per structural calculations. Please provide structural calculations for the structure and indicate anchor locations on a plan.
4. General: Please provide a site plan indicating the location of this structure. Provide separation distances from this structure to property lines, other buildings, etc. If this information is indicated on another sheet in this submittal, please reference this structure to that sheet.
5. General: Please provide written responses to all review comments.
06/19/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a address and mark or identification for the two electrical services. The plans show both of them as "SES". If the two "SES"s are located on the same parcel or address designate them per the Utility's requirement for metering clearance purposes.
#2. Ref; Plan Sheet E601. The feeder for well pump #13 (C601) has a ampacity rating at 130 amps. The OCPD protecting it is oversized at 200 amps. Please revise. NEC 310.15B(16).
#3. Ref; Plan Sheet E602. Indicate the feeder size for Panel 'W-11' and provide a fused disconnect ahead of the panel or main circuit breaker in panel 'W-11'. NEC 408.36b.
Dan Santa Cruz
Commercial Electrical Plan Review, City of Tucson
Dan.santacruz@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/03/2018 KROBLES1 OUT TO CUSTOMER Completed