Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM03851
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/23/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/06/2018 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 06/14/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet 0; Open Bay Office: The licensed structural engineer of record signed the original submittal of these documents on 9-22-12 with an expiration of his seal noted as 06/30/15. This information must be updated and the drawings must be restamped, signed, and dated. 2. Sheet 0; Open Bay Office (Applicable Codes): This list references the 2009 IBC, the 2009 IMC, the 2009 IECC, and the 2008 NEC. Please update these to the 2012 IBC, IMC, and IECC, and the 2011 NEC. Verify this submittal meets all of the requirements of the updated codes. 3. Sheet 6; Installation Instructions: Note 1 indicates anchors to be installed per structural calculations. Please provide structural calculations for the structure and indicate anchor locations on a plan. 4. General: Please provide a site plan indicating the location of this structure. Provide separation distances from this structure to property lines, other buildings, etc. If this information is indicated on another sheet in this submittal, please reference this structure to that sheet. 5. General: Please provide written responses to all review comments. |
| 06/19/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide a address and mark or identification for the two electrical services. The plans show both of them as "SES". If the two "SES"s are located on the same parcel or address designate them per the Utility's requirement for metering clearance purposes. #2. Ref; Plan Sheet E601. The feeder for well pump #13 (C601) has a ampacity rating at 130 amps. The OCPD protecting it is oversized at 200 amps. Please revise. NEC 310.15B(16). #3. Ref; Plan Sheet E602. Indicate the feeder size for Panel 'W-11' and provide a fused disconnect ahead of the panel or main circuit breaker in panel 'W-11'. NEC 408.36b. Dan Santa Cruz Commercial Electrical Plan Review, City of Tucson Dan.santacruz@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/03/2018 | KROBLES1 | OUT TO CUSTOMER | Completed |