Permit Number: T18CM03811
Parcel: 112030960

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T18CM03811
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2019 MCASTRO2 ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Mark Castro
Lead Planner

PROJECT:
T18CM03811
3002 E Richards Row
Bedroom, Bathroom, Laundry Room Addition

TRANSMITTAL: 3/28/19
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

Based on a wall height of 14'-5", the required setback to the east lot line is 9'-6", proposed is 8'-0".

DDO approval required prior to zoning approval.
04/18/2019 MCASTRO2 BUILDING-RESIDENTIAL REVIEW Needs Review