Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T18CM03787
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/21/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | The recommended method of addressing the structural deficiency of the cell tower by simply stating, "Further engineering and detailing will be required to determine an acceptable modification solution." is inadequate. Do the further engineering and detailing required to allow the installation of the proposed equipment to proceed without overstressing the cell tower. [Initial comment: The structural calculations indicate that section L3 of the tower shaft has insufficient capacity to support the proposed equipment modifications but no solutions have been presented. Determine an appropriate course of action and provide calculations and drawings needed to effect the solution to the problem.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/11/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |