Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM03787
Parcel: 99999999C

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM03787
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change The recommended method of addressing the structural deficiency of the cell tower by simply stating, "Further engineering and detailing will be required to determine an acceptable modification solution." is inadequate. Do the further engineering and detailing required to allow the installation of the proposed equipment to proceed without overstressing the cell tower. [Initial comment: The structural calculations indicate that section L3 of the tower shaft has insufficient capacity to support the proposed equipment modifications but no solutions have been presented. Determine an appropriate course of action and provide calculations and drawings needed to effect the solution to the problem.]

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2018 AVAUGHN1 OUT TO CUSTOMER Completed