Permit Number: T18CM03744
Parcel: 127035510

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM03744
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2018 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Approved
06/29/2018 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Item no. #2 of the plumbing review which requires structural details of the water heater platform is not addressed. This is not contained in the architectural plan as referred to by the mechanical engineer. Please provide. IBC 107.2.1
07/05/2018 SVALENZ1 MECHANICAL-COMMERCIAL REVIEW Needs Review
07/05/2018 SVALENZ1 ZONING REVIEW Needs Review
07/06/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. Unisex, or assisted use toilet facilities are only allowed to be used for credit toward the required number of plumbing fixtures where each toilet facility required to have only one water closet, and not more than two unisex toilet facilities are permitted to serve as the required separate toilet facilities. The calculated number of water closets for male and female use is 3 each, which would not allow the use of 3 unisex toilets to count towards the required number of separate facilities. IPC 403.2.1