Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM03744
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2018 | ERIC NEWCOMB | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/29/2018 | ERIC NEWCOMB | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Item no. #2 of the plumbing review which requires structural details of the water heater platform is not addressed. This is not contained in the architectural plan as referred to by the mechanical engineer. Please provide. IBC 107.2.1 |
| 07/05/2018 | SVALENZ1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/05/2018 | SVALENZ1 | ZONING | REVIEW | Needs Review | |
| 07/06/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | 1. Unisex, or assisted use toilet facilities are only allowed to be used for credit toward the required number of plumbing fixtures where each toilet facility required to have only one water closet, and not more than two unisex toilet facilities are permitted to serve as the required separate toilet facilities. The calculated number of water closets for male and female use is 3 each, which would not allow the use of 3 unisex toilets to count towards the required number of separate facilities. IPC 403.2.1 |