Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM03744
Parcel: 127035510

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM03744
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide an occupant load calculation breakdown of specific areas such as office, classrooms, breakroom, training and list the applicable occupant load factors. IBC Table 1004.1.2..
2. Provide plumbing fixture calculations per 2012 IBC Table 2902.1 based on a total occupancy load for this building to confirm the amounts of plumbing fixtures shown on the floor plans.
3. On the site plan; label the building where work occurs for this permit and show the distance from the adjacent building. IBC 107.2.1
4. Provide a demolition plan that show interior walls, ceilings, fixtures and exterior walls that will be demolished or modified. IBC 107.2.1
5. A minimum of 2-drinking fountains is required for use by standing persons and for people who use a wheel chair. IBC TABLE 2902.1.
6. Provide a door shedule of all newly installed doors; specify hardware types and note on plans "Doors shall be readily openable from the egress side without the use of a key or special knowledge." IBC 1008.9
7. Provide an enlarged plumbing floor plan and show all maneuvering clearances at plumbing fixtures. ICC 117.1 305.1.
8. Show the size and heights of grab bars and heights of plumbing fixtures, mirrors and dispensers. IBC 107.2.1
9. Show a detail of weep screeds at the bottom of the wall that complies with IBC 2512.1.2 Weep indicating 2" clearance from paved areas and 4" above earth.
10. Provide a listing of special inspections required for this project. IBC 1705.1
11. Specify the edition of the IBC for structural design. IBC 107.2.1
05/23/2018 KROBLES1 MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide an equipment schedule on the plans of all existing equipment. Show the sizes and capacities of the existing RTU's. IMC 106.3.1
2. Show on the plans duct materials and gages of new installed ductwork. Materials and gages shall be in accordance with ANSI, SMACNA or other industry approved agency. IMC 603.1
3. The heating and cooling duct system should be sized in accordance with one of the recognized methods of ASHRE, ACCA or other approved method. Specify and document the method used for sizing the duct system. IMC 603.2
4. Specify CFM for all supply registers. IMC 106.3.1
05/23/2018 KROBLES1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Provide compliance with the Tucson/Pima County Outdoor Lighting Code. If claiming exemption per section 401.2.1(3), verify full cut-off shielding.
2. Correct all references on KEYED NOTES to sheet E-1 to the proper reference sheet; Sheet E-1 not located on plans.
05/23/2018 KROBLES1 PLUMBING-COMMERCIAL REVIEW Reqs Change 1. If water heater is installed on a platform supported from the wall/roof, specify the weight of the WH and provide structural plan and calculations of platform construction. IBC 107.2.1
2. The bottle water dispenser does not meet the requirements for required drinking water as specified on TABLE 2902.1 or City of Tucson policy for point of use dispenser. Specify an approved method for providing drinking water to building occupants. IBC 2902.
3. Tempered water shall be delivered to lavatories for public toilets from an approved temperature limiting device. Specify on water plan. IPC 416.5
4. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for at least 10-seconds for accessibility. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
06/08/2018 KROBLES1 ENGINEERING REVIEW Passed
06/08/2018 KROBLES1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: 626 N. Craycroft Road
T18CM03744
Building Plan (1st Review)

TRANSMITTAL DATE: June 08, 2018

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. It appears that the propose canopy at the north end of the building effects the vehicle use area site. Development package DP18-0001 will need to be revised to show the changes to the site.

3. Until all other PDSD review agencies have approved the building plans zoning cannot approve.


Once the above comments are addressed Zoning will provide an over-the-counter review. Please call or email to schedule an appointment for this review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
06/08/2018 KROBLES1 WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/25/2018 FERNE RODRIGUEZ REJECT SHELF Completed