Permit Number: T18CM03701
Parcel: 118121260

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T18CM03701
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM03701
Master Bedroom Addition and Carport Area addition (1st Review)
235 E. 24th Street

TRANSMITTAL DATE: May 17, 2018

DUE DATE: May 31, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has done a review of the proposed building additions as it relates to the zoning review purview for residential development. It is acknowledged that a Design Development Option is required for the Carport addition attached to the new Master Bedroom. Address the following comments and it may be necessary to have the DDO plans re-stamped once the changes are made to the site plan.


2. COMMENT: The lot coverage calculations will have to be revised and additional information added as follows;

a. The guest house square footage is greater than 101 SF, it is approximately 800 SF.
b. The plans is noted with a porch attached to the new Master Bedroom but in actuality it should be named as carport as it allows for vehicle access to the rear yard.
c. The vehicular use area to the rear yard shall be delineated in order to determine the overall vehicle use area SF.
d. In order to verify that the lot coverage is correct the building footprints need to be dimensioned including the carport.
e. Maximum lot coverage is 75%.



If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Site Plan and Approved DDO plans set
06/06/2018 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T18CM03701
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

MECHANICAL PLANS:

1. Show sufficient appliance spacing such that each appliance (water heater) may be serviced or removed without removal of any other appliance (dryer), M1305.1.

ELECTRICAL PLANS:

1. Provide an electrical riser diagram, E3403. Notate the grounding and bonding method, E3607. Show the new sub-panel and feeder conductor size, Table E3704.2(1).

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/18/2018 LPEREZ2 OUT TO CUSTOMER Completed