Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM03688
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2018 | EHAMBLI1 | ZONING | REVIEW | Approved | |
| 05/21/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2012. |
| 05/21/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/21/2018 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
| 05/21/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a point of use dispenser in an accessible location; plumbed for water with cups located at dispener. CITY OF TUCSON POLICY |
| 05/21/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/21/2018 | QJONES1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 05/21/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/21/2018 | QJONES1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/21/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 05/21/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 05/21/2018 | QJONES1 | REJECT SHELF | Completed |