Permit Number: T18CM03687
Parcel: 10601004B

Address:
3939 N 1ST AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM03687
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. The structural calculations that have been submitted do not match the structural ftg. details on S1.0. The the reinforcement from "Strucalc" specify #4 rebar at 4.38" on center. The ftg. setails on S1.0 specify 12" o.c. for rebar placement.
2. Specify the type of wood post base for the wood post on detail 1.
3. The structural calculations also need to note the field weld on WF post on detail 2.
4. Provide a list of special inspections for this project.
07/06/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved