Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM03687
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/22/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code. #2. Provide load calcs for the electrical service. The plan shows 350 kcmil aluminum conductors feeding the service. These conductors are rated at 250 amps. Verify the service has the capacity for the additional load (Panel C). #3. Locate the Panels on the floor plans. Ref; 2012 IBC sec 107.2.1, 2011 NEC |
| 07/05/2018 | KROBLES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |