Permit Number: T18CM03687
Parcel: 10601004B

Address:
3939 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM03687
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2018 EHAMBLI1 ZONING REVIEW Approved
06/22/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/22/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code.
#2. Provide load calcs for the electrical service. The plan shows 350 kcmil aluminum conductors feeding the service. These conductors are rated at 250 amps. Verify the service has the capacity for the additional load (Panel C).
#3. Locate the Panels on the floor plans.
Ref; 2012 IBC sec 107.2.1, 2011 NEC
06/22/2018 EHAMBLI1 ENGINEERING REVIEW Passed
06/22/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet T1.0; Exiting Analysis: Per the IBC Table 1021.2(2), the maximum exit access travel distance is 75 feet. This table must be used since there is only one exit from the second floor (the second stair is being removed on this permit. Please verify.
2. Sheet A1.0; Main Floor Plan: Please add a note to reference the new lift.
3. Sheet S1.0; Framing and Foundation Plans: Please provide structural calculations for the framing and foundations required at the new lift.
4. General: Please provide written responses to all review comments.
06/22/2018 ROBERT SHERRY WATER REVIEW Completed
06/22/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/22/2018 JVINCEN1 FIRE REVIEW Approved
06/22/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed