Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM03687
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/22/2018 | EHAMBLI1 | ZONING | REVIEW | Approved | |
| 06/22/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 06/22/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code. #2. Provide load calcs for the electrical service. The plan shows 350 kcmil aluminum conductors feeding the service. These conductors are rated at 250 amps. Verify the service has the capacity for the additional load (Panel C). #3. Locate the Panels on the floor plans. Ref; 2012 IBC sec 107.2.1, 2011 NEC |
| 06/22/2018 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
| 06/22/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet T1.0; Exiting Analysis: Per the IBC Table 1021.2(2), the maximum exit access travel distance is 75 feet. This table must be used since there is only one exit from the second floor (the second stair is being removed on this permit. Please verify. 2. Sheet A1.0; Main Floor Plan: Please add a note to reference the new lift. 3. Sheet S1.0; Framing and Foundation Plans: Please provide structural calculations for the framing and foundations required at the new lift. 4. General: Please provide written responses to all review comments. |
| 06/22/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/22/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/22/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 06/22/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |