Permit Number: T18CM03643
Parcel: 12801033A

Address:
6211 E 22ND ST

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM03643
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the gas piping for the hot plate(#3). Is it a single connection for 424 CFH or 4 connections for 106 CFH each?
Coordinate with diagram A/P1.
2. Why was Table402.4 (2) used instead of Table 402.4 (3), IFGC 2012?
05/11/2018 EHAMBLI1 ZONING REVIEW Passed