Permit Number: T18CM03640
Parcel: 13426001B

Address:
710 S KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM03640
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet PV-0; Sheet Index: Please add the structural sheets S1, S2, S3, and S4 to the index.
2. Sheet PV-2; Side View (Carports 2, 3, and 4): Should the 25'-6" dimension at the roof be 25'-6 1/4" per the carport plans? Please verify.
3. Sheet PV-2; Side View (Carports 2 and 4): Should the 13'-4" dimension at the lower roof cantilever be 13'-4 1/4" per the carport plans? Please verify.
4. Sheet PV-2 (Side View Carports 1, 2, 3, and 4); Sheets S2 and S3 (Carport Sections A and B): The dimension for the clear height of the low end of the canopies indicates 8'-2" minimum clear height and maximum 9'-2" on the structural sheets, while the Side View indicates 8'-2" on Sheet PV-2. Please coordinate.
5. General: Please provide written responses to all review comments.
06/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the Tucson/Pima County Outdoor Lighting Code for the new proposed exterior lighting as required per section 104.2 of this code. This code can be printed or downloaded from www.tucsoaz.gov/pdsd.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/13/2018 LPEREZ2 OUT TO CUSTOMER Completed