Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T18CM03598
Parcel: 121110660

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T18CM03598
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/11/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide the outside air requirements for AC-1. [Initial comment: Infiltration may not be used to satisfy the required makeup air for the kitchen hood. Reference: Section 501.4, IMC 2012.]
2. Review the unit loads e.g. the hood weighs 589 pounds, not 521 pounds, the exhaust fan for the hood weighs 150 pounds, and the weight of a cook cleaning the hood was not included. [Initial comment: Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012.]
07/10/2018 AVAUGHN1 BUILDING-COMMERCIAL REVIEW Needs Review
07/10/2018 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed