Review Details: RESUBMITTAL - TI ALL
Permit Number - T18CM03598
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/11/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/11/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the outside air requirements for AC-1. [Initial comment: Infiltration may not be used to satisfy the required makeup air for the kitchen hood. Reference: Section 501.4, IMC 2012.] 2. Review the unit loads e.g. the hood weighs 589 pounds, not 521 pounds, the exhaust fan for the hood weighs 150 pounds, and the weight of a cook cleaning the hood was not included. [Initial comment: Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012.] |