Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2018 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T18CM03527 Duplex
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Indicate the location of the sewer lines between the county system and buildings, R106.1.1. Show the sewer line from the property through any easement and public roadways to the point of connection at Pima County waste system.

FLOOR PLANS:

1. Roof projections extending into the 3-foot fire separation distance require not less than one-hour fire-resistive construction on the underside. Provide notation for compliance with R302.1 (City of Tucson Amended) at the west overhang such as 5/8" type 'X' sheet rock placed on the underside of overhang rafters with edge protection of extended 2x fascia board. The fire protected overhang may not extend closer than 24" from the property line.
2. Individual dwelling units in duplexes must be separated by 1-hour fire-resistance rated assemblies from floor to bottom of roof sheathing, R302.3. Provide a detail or notation showing compliance with R302.3 for the existing separation wall and proposed wall. Assure attic separation with appropriate fire barrier over the existing wall.
3. Show the location of a minimum 22" x 30" attic access for each unit, R807.1.

MECHANICAL PLANS:

1. Show dryer vent size and location for venting to exterior, M1501.
2. Show bathroom exhaust fan locations with minimum 50 CFM rating and duct to the exterior, R303.3 and M1507.4.

ELECTRICAL PLANS:

1. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
2. Show receptacle outlets at each kitchen counter space wider than 12" with no point along the wall line more than 24" from a receptacle outlet, E3901.4.1. Show receptacles within 2' of counter edges or corners and no more than 4' apart.
3. Protect all interior 15A & 20A proposed outlets (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12.
4. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
07/23/2018 JOHN VAN WINKLE ENGINEERING REVIEW Passed
07/24/2018 AVAUGHN1 ZONING REVIEW Needs Review