Permit Number - T18CM03316
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/09/2018 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T18CM03316 - PLAN REVIEW COMMENTS Reviewer: Chris Anderson, May 8, 2018 BUILDING – COMMERCIAL On the code analysis, sheet A.1, it says that restrooms are located on site in adjacent building. Show where they are located on the site plan and provide plumbing calculations for the adjacent building to show that the facilities are adequate for both the existing building and new welding shop. Ref. 2012 IBC Table 2902.1. It appears from the wall sections on sheet A.2 that the R-30 roof and wall insulation will be new. This arrangement is not prescriptive to the 2012 IECC Table C402.2. Submit a building envelope COMcheck that includes exterior walls, roof and all doors. The R-30 insulation shall be shown as “cavity” in the COMcheck. Also include the selected door U-factors in the door and hardware schedule. These U-factors must be the same as shown in the envelope COMcheck. Enlarge the scrim information box on sheet A.2 so that the text is minimum 3/32” to comply with City of Tucson standard. Item K on sheet A.6 is “MSDS HAZMAT cabinet.” Please provide information on hazardous materials and quantities to be reviewed per 2012 IBC Section 415. |
05/09/2018 | FRODRIG2 | WATER | REVIEW | Approved | PER CHRIS ANDERSON |
05/09/2018 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | PLUMBING – COMMERCIAL Per 2012 IMC 928.1 (4) the evaporative cooler shall have potable water backflow prevention. |
05/09/2018 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/09/2018 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | MECHANICAL – COMMERCIAL Per 2012 IMC 928.1 (5) the building shall have air intake openings for proper functioning of the evaporative cooler located per 2012 IMC 401.4. |