Permit Review Detail
Review Status: Active
Review Details: CELL TOWER/ANTENNAS
Permit Number - T18CM03291
Review Name: CELL TOWER/ANTENNAS
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 08/07/2018 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 08/08/2018 | ROBERT SHERRY | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 08/29/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/01/2018 | ANY | APPROVAL SHELF | RECEIVED |