Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM03288
Parcel: 125101480

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM03288
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2018 MARTIN BROWN FIRE REVIEW Approved
05/15/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. ON THE PLANS; SPECIFY THE OCCUPANCY CLASSIFICATION AND TYPE OF CONSTRUCTION. IBC 302.1, 602.1.
2. SELF-SERVICE CONCESSION STANDS FOR FOOD AND DRINK SHALL BE ACCESSIBLE. PROVIDE REQUIRED OBSTRUCTED AND UNOBSTRUCTED REACH DEMENSIONS. ICC A117.1 308.2.2, 308.3.1, 308.3.2.
3. OPERABLE PARTS FOR MACHINERY AND EQUIPMENT REQUIRED TO BE ACCESSIBLE SHALL COMPLY WITH SECTION ICC A117.2.1. 308 AND 309.
4. THE NEW PARTIALLY ENCLOSED CONCESSION AREA IS REQUIRED TO BE ACCESSIBLE. ENTRY INTO THE CONCESSION WORK AREA SHALL BE THROUGH OPENINGS NOT LESS THAN 36-IN. IN WIDTH. SHOW DIMENSIONS OF OPENINGS. A117.1 404.1,
5. THE WORK AREA OF THE NEW CONCESSION IS REQURIED TO BE ACCESSIBLE BECAUSE IT EXCEEDS 300 S.F., SHOW DIMENSIONED MANEUVERING CLEARANCES. IBC 1103.2.3.
6. SPECIFY AND DETAIL HOW NEW PARTITIONS AND BENCH SEATING IS ANCHORED TO SLAB. IBC 106.2.1
05/21/2018 ROBERT SHERRY WATER REVIEW Completed
05/22/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a direct waste connection for the hand sink (38A, currently shown with an indirect connection to a hub drain). Reference: Sections 301.3 and 802.1, IPC 2012.
2. Provide separate indirect waste pipes for each food-handling fixture to protect against cross-contamination or fouling. Reference: Section 801.2, IPC 2012.
3. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
4. Indirect waste receptors (e.g. the hub drain for the water heater) shall not be installed in inaccessible or unventilated spaces (e.g. cupboards, storerooms, or closets). Indirect waste receptors shall have ready access. Reference: Section 802.3, IPC 2012.
05/22/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/30/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved