Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM03156
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2018 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 05/25/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/25/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | 1. Sheet PV1.2 (P2 Profile); Sheet S3.0 (P2 Elevation): The P2 Profile indicates a 34'-1 3/4" total array length and a 12'-11" array height at the high end, while the P2 Elevation indicates a 34'-3" length and a 12'-9" height at those same locations. Please coordinate. 2. Sheet S2.1; P1 and P2 Array Plans: The purlin call-out on P1 indicates (2) 1000S250, while the purlin call-out on P2 indicates a single purlin. The purlin calculations on each structure indicate a "Single C Stud". Please verify the plans are correct for the purlin call-outs. 3. General: Please provide written responses to all review comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/24/2018 | LPEREZ2 | OUT TO CUSTOMER | Completed |