Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM03069
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/24/2018 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
04/24/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
04/24/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/24/2018 | BLARSON1 | ENGINEERING | REVIEW | Passed | PASSED BY STEVE |
04/24/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/24/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
04/24/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Relocate the gas shutoff valve (detail 14) to a location upstream of the dirt leg. reference Section 408.4, IFGC 2012. 2. Provide separate indirect waste pipes for each compartment of the 4-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. |
04/24/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/24/2018 | BLARSON1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/19/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |