Permit Number: T18CM03027
Parcel: 136326730

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM

Permit Number - T18CM03027
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2018 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: T18CM03027
4725 S. Paseo Melodioso
New SFR
Residential (1st Review)

TRANSMITTAL DATE: May 7, 2018

The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

This site is located in the R-1 zone (UDC 4.7.8). An Single Family Residence is an allow use in this zone.

1. Until the grading plan, DP18-0101 is approved Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
05/14/2018 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
05/15/2018 MARTIN BROWN FIRE REVIEW Reqs Change Fire sprinklers required. Please add note to plan indicating installation of fire sprinklers will be a deferred submittal.
(low fire flow, further than 150' deep with no turnaround, slope of road exceeds allowable for access)
05/25/2018 LOREN MAKUS ENGINEERING REVIEW Reqs Change The grading plan must be approved first.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/13/2018 LPEREZ2 APPROVAL SHELF Completed
06/13/2018 LPEREZ2 OUT TO CUSTOMER Completed
06/13/2018 LPEREZ2 REJECT SHELF Completed