Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM02983
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/09/2018 | GPERU1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the sum of ratings of overcurrent protection devices and the new 400 amp switch does not exceed 120 percent of the busbar rating of the existing service panel. NEC 803.1 2. The position of the back fed switch from the PV inverters requires a connection at the opposite end of the busbar from the input feeder location or main circuit breaker. NEC 705.12 3. Submit specification and electrical data sheets on inverters, PV modules and all associated equipment. 4. Verify that terminations, circuit breakers and equipment is rated for 90 degree ampacity rating of TABLE 310.16. NEC 110.14 5. The equipment ground size for 400 amp over current protection is No. 3 awg. per NEC TABLE 250.122 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/23/2018 | SVALENZ1 | OUT TO CUSTOMER | Completed |