Permit Number: T18CM02883
Parcel: 10511061R

Address:
4500 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM02883
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/20/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Guard rails are required along the section of building perimeter walls where the solar array is built up against. The guard rails are required because personel require access to do maintenance on the solar equipment at the exterior wall location. IBC 1013.1
2. Provide a grard rail detail that shows the 42" height and attachment to the building. IBC 107.2.1