Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM02883
Parcel: 10511061R

Address:
4500 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM02883
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S-101; Site Plan: Please indicate on the plan the distance from the edge of the new canopies to the edge of the existing roof.
2. Sheet S-301; Sections A1 and E1: For maintenance personnel on the new structure, the requirements of the IBC Section 1013.2 (guardrails) must be met. Please provide structural calculations and details for the rail design and the connection to the new canopy.
3. Sheet S-402: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the verbiage size in the details.
4. Sheet S-404; Grout Pad Detail G3: Please provide specifications on this detail for the non-shrink grout.
5. General: Please provide written responses to all review comments.
06/04/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref: Plan Sheet E142, E402. The three line diagram shows the inverters having DC and AC disconnects, however the inverter spec sheet only refers to a DC disconnect. If the inverters do not have an integral AC disconnect, please provide for a disconnect to be installed within site and no further than 50 feet from the inverter as applicable per NEC 690.14D.
#2. Provide full compliance with Tucson/Pima County Outdoor Lighting Code for the exterior lighting. This code can be printed or downloaded from www.tucsonaz.gov/pdsd.
#3. Enlarge the manufacturer cut sheets to a 3/32" font size or larger. The lettering is small.
#4. Provide a signed letter and name of a contact person from the manufacturer of the electrical service equipment with a statement that the proposed line side PV interconnection will not compromise the listing or performance of the equipment. Include a shop drawing showing the exact location of the tap, along with hardware used. Or provide for an NRTL field evaluation and re-listing of the equipment after the tap is performed.
Ref: 2012 IBC sec 107.2.1, 2011 NEC, 2012 Tucson/Pima County Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2018 SVALENZ1 OUT TO CUSTOMER Completed