Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM02839
Parcel: 106101060

Address:
4010 N RUNWAY DR

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T18CM02839
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2018 MARTIN BROWN FIRE REVIEW Approved
04/30/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide minimum plumbing fixture calculation in accordance with IBC TABLE 2902.1
2. The occupant load listed in the CODE ANALYSIS does not match the number given in the OCCUPANT LOAD TABLE. State the correct occupant load. IBC TABLE 1004.1.2
3. Provide a list of SPECIAL INSPECTIONS for this project. IBC 1705.1
4. A parapet is required on the fire resistive exterior wall that butts against the property line. Parapet construction must be 2-hr fire resistive and extend 30 inches above the roof line. IBC 705.11.1
5. Provide a listed assembly of the 2-hr. fire resistance rated wall. IBC 703.1
6. Building thermal envelope shall comply with the requirements of the IECC for insulation, fenestration and material performance. Submit verification of compliance. IECC C402
7. Provide a listed assembly of the wall to roof connection. IBC 703.1
8. The minimum ceiling height in the bathroom is required to be 7 ft. Provide dimensions of the ceiling height and slope; the bathroom is also requird to be accessible so compliance with ICC A117.1 sec. 307.4 is required. IBC 1208.2
9. The walls and soffits within enclosed usable spaces (bathroom) under encolsed or open stairways shall be protected by 1-hour fire resistive rated construction. Submit listed assembly penetrations for fans, lights or other. IBC 1009.9.3
10. Provide a stair profile; show dimensioned details of the risers, treads, handrail and guardrail. IBC 1009.7, 1012.1 1013.1
11. The stair handrail is required to extend 12-in. beyond the top and bottom riser and turned into the wall. IBC 1012.6
12. Provide a reflected ceiling plan of the entire building and show EXIT and emergency lighting and air registers. IBC 1006.3, 1011.1, 107.2.1
13. Provide drinking fountains with spout outlets for accessible wheelchair access and standing persons. ICC A117.1 602.4
05/08/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the size of the water service pipe to the building. On sheets C1.0 and P1.0 it is 1" but on sheet A1.0 it is 1-1/4"
2. Correct the notation on the water heater detail on sheet P1.0 that states that a thermal expansion tank is not required if an RPA is installed. See Section 607.3.2, IPC 2012.
3. Based on the Private Grading & Paving document (Development package DP17-0054, sheet C2.0), the rim elevation of the next upstream sanitary manhole (9722-02, 2271.63) is less than 12" below the first floor elevation (2272.50'). Provide a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
4. Provide cleanouts for the building sewer located not greater than 100-feet apart, measured from the upstream entrance of the cleanout. Reference: Section 708.3.1, IPC 2012.
5. Provide a final cleanout for the building sewer located at the property line. See Pima County Wastewater Reclamation detail RWRD 401, HCS Connection to Sewer Line.
6. The plumbing plans calls for a 3" building drain and a 3" building sewer. At what point will the building sewer change to 4" as shown on sheet C1.0? Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012.
05/09/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the building envelope, mechanical systems, and the interior lighting using COMcheck. Reference: Sections C101.3, C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2012.
2. Show how one of the "Additional Efficiency Package Options" (C406, IECC 2012) is to be accomplished. Reference: Section C401.2, IECC 2012.
3. All U-values and Solar Heat Gain Coefficients (SHGC) for fenestration assemblies (i.e. doors, windows, etc.) shall be NFRC-certified. Reference: Section C303.1.3, IECC 2012.
4. Verify that the specified HVAC systems are provided with controls that are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy. Reference: Section C403.2.4.3.3, IECC 2012.
5. Show that the connection of the outside air ducts to the indoor air handlers is being made in accordance with the conditions of product listing and the manufacturer's installation requirements. Reference: Section 304.1, IMC 2012.
6. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Provide justification for the "Tucson, AZ Safety Factor." Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012.
7. Secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.10, IMC 2012.
05/09/2018 ROBERT SHERRY WATER REVIEW Reqs Change State the size and type of backflow prevention assembly that is being installed for the building water service.
05/10/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM02839 - Construction Service Use - I-1 Zoning
Building Plans (1st Review)
4010 N Runway Drive

TRANSMITTAL DATE: May 10, 2018

DUE DATE: May 15, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package. While the building footprint is consistent with the approved DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: As part of the zoning review purview it was noted that the building plans include a Mezzanine level that was not included in the development package. While the mezzanine does not extend beyond the building footprint it is counted as building square footage and is subject to compliance for vehicle and bicycle parking. Prior to any approval of the building plans the development package will have to be revised to address the additional building square footage.

In addition, the building height listed on the DP is 18 feet. However the building cross section lists the overall height from FF at one end at 20 feet and 18 feet at the lower end. Building height as defined in the UDC is the vertical distance measured from the design grade elevation to the highest point of a flat roof; to the deck line of a mansard roof; or to the middle (between the eave and ridge) of the highest gable of a pitched or hipped roof, except as follows: (See Figure 6.4.4-A, Measurement of Building Height.) The height of the building will have to be revised on the DP as well as measured from design grade.

3. COMMENT: Assure that the approved and signed revised copy of the DP is included in the next submittal of the building plans or remove the current DP plan set from the building plans set and reference the DP case number on the Architectural site plan.

4. COMMENT: Zoning will review the building plans on the next submittal to assure that any revisions made to the building plans do not affect zoning requirements and that the above comments have been addressed. Zoning will also review for compliance with revised DP.

5. COMMENT: Zoning will not be able approve the building plans until a revised DP has been processed and approved by PDSD.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
05/14/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1 Provide complete compliance with the 2012 IECC for the lighting.
#2 Verify light source color temperature for the exterior lighting is not exceeding 3500K per sec 402.1 Tucson/Pima County Outdoor Lighting Code.
05/17/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T18CM02839

1) Show on plans that any roof drains (downspouts) scupper underneath sidewalks or pedestrian walkways. Reference City of Tucson Technical Standard (TSM) 7-01.4.1.E.
2) Floodplain use permit and Elevation Certificate will be issued once building plans are approved
3) Per zoning comments a revised development package (DP) is required. Building plans will be approved once the revised DP has been approved

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007

Final Status

Task End Date Reviewer's Name Type of Review Description
05/23/2018 LPEREZ2 OUT TO CUSTOMER Completed