Permit Number: T18CM02829
Parcel: 13013044B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T18CM02829
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the proposed duct revision that shows a supply duct connected directly to the return plenum of FC-1.
06/01/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. The Delta 3 is clouding in 2 spare circuit breakers #5 and #7 along with CU-1, #2, #4, #6 in panel 'P1'. Please clarify as to the scope of work for this revision.
Ref; 2012 IBC sec. 107.2.1
06/01/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/13/2018 LPEREZ2 OUT TO CUSTOMER Completed