Permit Number: T18CM02756
Parcel: 13355231B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM02756
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref: Lumen Calcs.
(a) The option used is for LPS lighting only. The proposed lighting changes include LED. Please revise and use the correct applicable option.
(b) If the total lumens exceed 100,000 per acre or 75% of the allowed lumens, a special inspection will be required. Sec 106.2.1
(c) Any exempt lighting (full cut-off under canopy- 3500K ) do not need to be included in the lumen calcs.
Ref: Tucson/Pima County Outdoor Lighting Code.
Dan.santacruz@tucsonaz.gov
06/06/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed