Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM02756
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/24/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/07/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the classification for interior wall and ceiling finish materials for fire performance and smoke development characteristics in accordance with IBC 803.1 2. Specify fire retardant treated wood for wall and ceiling finish material of plywood or wood cladding used on interior walls and partitions. IBC 603.1 |
| 05/11/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/14/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1 Plan Sheet E 382, is not indicated in the Sheet Index G001. #2 New Panel LP14 could not be located on the electrical floor plans. #3 Provide electrical load calcs for the electrical service including the new panels. #4 Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for any modifications to the exterior Lighting. Ref: 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements ( Electrical ). |
| 05/15/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/15/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations that justify the capacities of the new heating and cooling equipment specified for the project. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012. 2. Clarify the schedule for RTU-4. A design condition of absolute zero is not typically found in Tucson; this isn't Minnesota. Reference: Section 107.2.1, IBC 2012. 3. Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/24/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 05/24/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 05/24/2018 | QJONES1 | REJECT SHELF | Completed |