Permit Number: T18CM02756
Parcel: 13355231B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM02756
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2018 MARTIN BROWN FIRE REVIEW Approved
05/07/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide the classification for interior wall and ceiling finish materials for fire performance and smoke development characteristics in accordance with IBC 803.1
2. Specify fire retardant treated wood for wall and ceiling finish material of plywood or wood cladding used on interior walls and partitions. IBC 603.1
05/11/2018 ROBERT SHERRY WATER REVIEW Completed
05/14/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1 Plan Sheet E 382, is not indicated in the Sheet Index G001.
#2 New Panel LP14 could not be located on the electrical floor plans.
#3 Provide electrical load calcs for the electrical service including the new panels.
#4 Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for any modifications to the exterior Lighting.
Ref: 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements ( Electrical ).
05/15/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/15/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the new heating and cooling equipment specified for the project. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012.
2. Clarify the schedule for RTU-4. A design condition of absolute zero is not typically found in Tucson; this isn't Minnesota. Reference: Section 107.2.1, IBC 2012.
3. Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/24/2018 QJONES1 APPROVAL SHELF Completed
05/24/2018 QJONES1 OUT TO CUSTOMER Completed
05/24/2018 QJONES1 REJECT SHELF Completed