Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations justifing the AC system being installed.
2. Verify that the two specified bathroom exhaust fans can operate at the desired flow rate using a single 3" duct.
3. The specified range hood is designed for an island application and requires the use a 6" duct.