Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM02690
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/12/2018 | MMORENO1 | ZONING | REVIEW | Approved | |
| 04/12/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/12/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Plan Sheet E0.1 not stamped by Registrant. #2. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code for the Exterior Lighting. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. #3. The permit needs to reflect both addresses for the two electrical services shown on the plans. 2012 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code |
| 04/12/2018 | MMORENO1 | ENGINEERING | REVIEW | Passed | |
| 04/12/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/12/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/13/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 04/17/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G1.01; Sheet A2.01; Floor Plans: The existing restroom is not required to be accessible. The new restroom (water closet and sink are functional) must be accessible, but does no appear to be accessible per the ICC/ANSI Section 604.3.3. Please verify. 2. Sheet A10.01; Partitions: Interior partitions are required to resist lateral loads of 5 psf over the height of the wall. Add diagonal bracing at the top of the partitions, or provide structural calculations indicating partitions meet that criteria without bracing. If bracing is used, indicate the bracing size and spacing, and indicate the size and quantity of connectors at the top of the partition and to the structure above. |
| 04/17/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |