Permit Number: T18CM02662
Parcel: 122160010

Address:
3645 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM02662
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2018 MARTIN BROWN FIRE REVIEW Approved
04/27/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/07/2018 SSHIELD1 ENGINEERING REVIEW Passed
05/07/2018 STEVE SHIELDS ZONING REVIEW Passed
05/09/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a note for the under canopy lighting to verify compliance for the Tucson/Pima County Outdoor Lighting Code.
#2. Ref: Plan Sheet E4.2. Include all the Warning Labels specified throughout the electrical plans. Mark all Labels to correlate with the electrical equipment shown on the electrical plans.
Ref: 2012 IBC 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code.