Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM02662
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/18/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/27/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/07/2018 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 05/07/2018 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 05/09/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide a note for the under canopy lighting to verify compliance for the Tucson/Pima County Outdoor Lighting Code. #2. Ref: Plan Sheet E4.2. Include all the Warning Labels specified throughout the electrical plans. Mark all Labels to correlate with the electrical equipment shown on the electrical plans. Ref: 2012 IBC 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code. |