Permit Number: T18CM02661
Parcel: 12108001B

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T18CM02661
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/20/2018 ROBERT SHERRY WATER REVIEW Reqs Change My apologies, I am requesting information about the public water meter owned by Tucson Water and its backflow preventer. [Initial comment: Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012.]
04/20/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The proposed Sloan SF-2200 faucet has 2 options for time-out settings, 7-seconds and 70-seconds. For accessibility, the shortest time-out setting must be for at least 10-seconds. At a flow rate of 0.5 GPM, a 70-second time-out will deliver 0.58-gallons per cycle. State how the lavatory faucet will be limited to a deliver of 0.25-gallons per cycle. [Initial comment: Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.]
2. The shut off valve is still shown in the water heater detail. [Initial comment: Explain how the installation of a shut-off valve for the thermal expansion tank complies with the installation instructions. Reference: Section 303.2, IPC 2012.]
04/20/2018 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/20/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/20/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed