Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM02661
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/11/2018 | KELLY LEE | ZONING | REVIEW | Approved | |
04/11/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson. 2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2012. |
04/11/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide full compliance with the 2012 IECC for the lighting. Also revise the restroom exhaust fan controls per the Mechanical review comments. |
04/11/2018 | KLEE1 | ENGINEERING | REVIEW | Passed | |
04/11/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide third-party listing and material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012. 2. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 3. Explain how the installation of a shut-off valve for the thermal expansion tank complies with the installation instructions. Reference: Section 303.2, IPC 2012. 4. Show that the floor drain used as indirect receptors for water heater drain and the temperature & pressure relief is capable of accepting the maximum discharge and is designed to prevent splashing or flooding. Reference: Section 802.3.1, IPC 2012. |
04/11/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012. |
04/11/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/12/2018 | KROBLES1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Drinking fountain required. gp 2. Provide ADA sales counter. gp 3. Specify emergeny egress lighting. gp |
04/19/2018 | BLARSON1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |