Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM02650
Parcel: 11202034D

Address:
2155 E ALLEN RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM02650
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2018 MMORENO1 ZONING REVIEW Passed
04/11/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/11/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/11/2018 MMORENO1 ENGINEERING REVIEW Passed
04/11/2018 DAN SANTA CRUZ BUILDING-COMMERCIAL REVIEW Passed No Stuctural work
04/11/2018 ROBERT SHERRY WATER REVIEW Completed
04/11/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/11/2018 MARTIN BROWN FIRE REVIEW Approved
04/11/2018 BLARSON1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed