Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T18CM02625
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/17/2018 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T18CM02625 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. SECTIONS - DETAILS: 1. Show wood framing members resting on concrete as pressure treated, R317.1 item 2. Update detail 101. 2. Calculate and show the attic ventilation opening size using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. 3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. ELECTRICAL PLANS: 1. Protect all interior 15A & 20A proposed outlets (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12. Update note #13 with "bedroom" limitation. 2. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14. 3. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Show energy values on the plans consistent with values entered on RES check calculations, N1105.6. Update the R-30 ceiling insulation shown on detail 204. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/07/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |