Permit Number: T18CM02602
Parcel: 140260440

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM02602
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment: Please indicate on the drawing the explanation given in the response letter for unlimited area.
2. Previous Comment: Please provide a calculation for the required plumbing fixtures. Is this a change of use? The new plumbing calculations must be included since the size and occupant load has increased.
3. Previous Comment: Please provide a life safety egress plan in this submittal.
4. Previous Comment: Are there any new wall openings in this submittal? Please indicate on this plan, provide new details for that opening, and provide structural calculations for the framing around the opening.
5. Sheet IA1.0; Keyplan: The Keyplan indicates the wrong area for the plan. Please revise.
6. Sheet IA1.1; Keyplan: The Keyplan indicates the wrong area for the plan. Please revise.
7. General: Please provide written responses to all review comments.
06/13/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/13/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed