Permit Number: T18CM02600
Parcel: 14026045A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM02600
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 2; Sheet IA0.0: Please calculate on this sheet the maximum allowable SF for the combined spaces. Reference the IBC Chapter 5.
2. Previous Comment 3; Sheet IA1.0: Are there any new walls being constructed in this permit?
3. Previous Comment 6: Provide structural calculations for the wall opening between suites.
4. Sheet IA0.0; Plumbing Calculations: Per the IBC Section 2902.1.1, the total occupant load shall be divided in half, and plumbing fixtures shall be determined for each sex. For the B portion, we have 18 males and 18 females, which requires one water closet for each sex. For the S portion, we have 30 males and 30 females, which requires one water closet for each sex. The plan on Sheet IA1.0 only indicates one restroom indicating Men's. A minimum of two of the single water closet restrooms must be designated as Women's. Please revise Sheet IA1.0 with this information.
5. Sheet IA0.0; Building Scope: Are Suites 156 and 164 being combined into one suite? Please verify. Pima County addressing must make a change for this.
6. Sheet A0.1; Life Safety Plan: In the office area, the exit doors must be separated a minimum of 31'-4" (per the plan calculation). The two doors in that area do not meet the requirement, but do not need to meet it since a second exit (out of the storage area) is provided.
7. General: The licensed professional must sign and date all sheets.
8. General: Please provide written responses to all review comments.
06/13/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed