Permit Number: T18CM02600
Parcel: 14026045A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM02600
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2018 KELLY LEE ZONING REVIEW Approved
04/11/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/11/2018 ROBERT SHERRY ELECTRICAL-COMMERCIAL REVIEW Passed
04/11/2018 KLEE1 ENGINEERING REVIEW Passed
04/11/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/11/2018 ROBERT SHERRY WATER REVIEW Completed
04/11/2018 MARTIN BROWN FIRE REVIEW Approved
04/12/2018 KROBLES1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Wrong codes are referenced on the Title Sheet.
2. Provide the maximum allowable area for combining 2 suites for the type of construction and occupancy.
3. Show construction details of all new walls.
4. Provide minimum plumbing calculations.
5. Specify the type of construction for the walls that will be demo.
6. Provide structural calculations for the wall opening between suites.
7. Provide construction framing details for new wall openings.
8. Provide a life safety egress plan; indicate common path of egress travel measurements and maximum travel distance.
9. Provide enlarged ADA restroom floor plan; show all clearance measurements and provide wall elevations of grab bars, dispensers, mirrors and fixture heights.
10. Provide ADA shower detail cut sheets.
11. Submit a door schedule.
12. Provide required number of ADA parking stalls, submit measurements.
13. Keynote #3 references the City of Mesa building code; correct jurisdiction.
06/13/2018 LPEREZ2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review